DEHNcombo YPV …

Combined lightning current and surge arrester for use in photovoltaic power supply systems up to 1500 V d.c.

Categories: ,

Description

Technical data

SPD according to EN 61643-31 / IEC 61643-31 type 1 + type 2 / class I + class II
Max. PV voltage [DC+ -> DC-] (UCPV ) ≤ 1500 V
Max. PV voltage [DC+/DC- -> PE] (UCPV ) ≤ 1500 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Total discharge current (8/20 µs) [DC+/DC- -> PE] (Itotal ) 40 kA
Total discharge current (10/350 µs) [DC+/DC- -> PE] (Itotal ) 12.5 kA
Lightning impulse current (10/350 µs) [DC+ -> PE/DC- -> PE] (Iimp ) 6.25 kA
Voltage protection level [(DC+/DC-) -> PE] (UP ) < 4.5 kV
Voltage protection level [DC+ -> DC-] (UP ) < 4.5 kV
Response time (tA ) ≤ 25 ns
Operating temperature range (TU ) -40 °C … +80 °C
Operating state / fault indication green / red
Number of ports 1
Cross-sectional area (min.) 1.5 mm2 solid / flexible
Cross-sectional area (max.) 35 mm2 stranded / 25 mm2 flexible
For mounting on 35 mm DIN rails acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Place of installation indoor installation
Degree of protection IP 20
Dimensions 4 module(s), DIN 43880
Approvals KEMA, UL
Extended technical data: ———————————
– Use in DC battery storage systems up to ISCCR ≤ 100 kA (t ≤ 5.83 ms)
– Backup fuse for DC battery storage systems up to ISCCR Bussman HLS 2000Vdc / 200 A 2+/A173 DST aR, manufacturer’s Part. No.: 170M2040
– Backup fuse for DC battery storage systems up to ISCCR Mersen Protistor D122SD20C200QF 200A 2000V DC aR