Electrical parametersofDC surge protector FV20C/3-1000PV
| Model. No. | FV20C/3-1000PVS |
| SPD protection conforms to EN50539-11/IEC61643-31 | Type 2 |
| SPD installation type conforms to EN50539-11/IEC61643-31 | ClassII |
| Protection level conforms to DIN VDE0675-6 | C |
| Type of Network | Photovoltaic systemsDC side |
| Protectionmode | (+/-)–>PE , (-/+)–>PE, (+/-)–>(-/+) |
| Nominal Voltage UN | 1000 Vdc |
| Maximum continuous operating voltage for PV application UCPV | 1200Vdc |
| Short-circuit current rating ISCPV | 100A |
| Continuous operating current ICPV | <20 µA |
| Rated load current IL | 80 A |
| Residual current IPE | ≤20 µA dc
≤500 µA ac |
| Standby power consumption PC | ≤25 mVA |
| Maximum discharge current (8/20μs) Imax | 40 kA |
| Nominal discharge current (8/20μs) In | 20 kA |
| Voltage protection level Up | ≤3.6 kV |
| Isolation resistance Risol | >1000 MΩ |
| Response time tA | ≤25 ns |
| Remote control contact | YES |
| Disconnection indicator | Mechanical indicator
(Green: OK, Red: Replace) |
| I/O Connections | By screw terminal:10-35mm2
By connection bus |
| Installation location | Inside |
| Mounting type | Symmetrical rail (EN50022/DIN46277-3) |
| Color | Gray |
| Degree of protection | IP20 |
| Housing material | UL94V-0 |
| Ambient temperature | -40°C ~+80°C |
| Altitude | ≤2000 m (amsl (above mean sea level)) |
| Permissible humidity | 30%~90% |